REQUIREMENTS FOR THE INSTALLATION OF SMOKE DETECTORS
IN ONE/TWO FAMILY DWELLINGS IN ACCORDANCE WITH N.J.A.C. 5:70-4.19
- All
smoke detectors shall bear label showing the detector has been tested
in accordance with Underwriters Laboratories Standard 217.
- All
smoke detectors shall be either battery operated or permanently wired
to a non-switchable circuit of the house current. Plug units are permitted
if a restraining device is used at the plug and the outlet is not controlled
by a wall switch.
- All
equipment shall be so located that accidental activation will not be caused
by jarring or vibration.
- All
equipment shall be so located that accidental activation will not be caused
by jarring or vibration.
- All
equipment shall be affixed to the wall or ceiling surface in accordance
with the manufacturers recommendations.
- At least one detector shall be installed on each level of the dwelling. If there are separate sleeping areas on any level, additional detectors are required in the immediate vicinity of each sleeping area.